This manual details the installation, operation, technical parameters, troubleshooting, and maintenance of the DSN3 series indoor electromagnetic locks for…
The document describes the DSN3 series indoor electromagnetic lock, a device designed to prevent electrical misoperation in high-voltage equipment such as fixed-type switch cabinets and handcart cabinets. It is specifically applicable for locking mechanisms of disconnect switches and grounding devices, particularly compatible with WBF-III type microcomputer locking systems.
The manual provides comprehensive instructions covering the product's structure (including cabinet door, knife switch, and grounding locks), working principles based on intermittent suction, detailed installation methods for various components, operational procedures, troubleshooting guides for common faults like indicator light failure or unreliable locking signals, and maintenance requirements. This manual is written in Chinese.
| Operating Temperature Range | +40°C to -10°C (High cold region: -25°C) |
|---|---|
| Maximum Altitude | 2500m |
| Relative Humidity (Daily Average) | Not greater than 95% |
It serves as a locking device to prevent electrical misoperation in indoor high-voltage switchgear, specifically for disconnect switches and grounding devices.
In special situations where the lock must be opened without voltage, a dedicated unlocking key can be used to release it.
This indicates a faulty indicator light. The cover plate can be removed to replace it, ensuring a 200kΩ resistor is connected in series.