This manual provides installation and operation instructions for Xylem Moisture Sensor Relays (models 9K583, 9K584, and 9K585) compatible with various…
The document serves as an installation and operation guide for the Xylem Moisture Sensor Relay. It details safety instructions regarding electrical grounding and code compliance before connecting the device to pump controllers.
The manual provides specific wiring diagrams and connection steps for integrating the sensor with multiple controller models, including Aquavar SOLO/SOLO2, AB2, S-Drive, SPD, e-SM Smart Motor, IPC, and Hydrovar. It covers single sensor connections as well as configurations for connecting two sensors in series.
| Operating Current | 10 mA |
|---|---|
| Contact Resistance | 100 mΩ |
| Switching Voltage Max | 30 Volts DC |
| Switching Current Max | 500 mA |
The Red and Black wires power the switch, while the White and Green wires serve as the relay output.
Connect the green wire from sensor 1 to the white wire of sensor 2, then connect both sensors' black/red wires to the transducer terminal.
Disconnect and lockout electrical power, ensure all exposed metal piping is grounded, and have work performed by a qualified technician.