Selection manual for Xinwei AMDW-□/A series motor protectors covering features, technical data, fault codes, parameters, wiring and dimensions.
Xinwei AMDW-□/A series motor protectors are three-phase AC motor protectors for rated voltage 1140 V and 50/60 Hz. The manual covers product features, technical data, fault codes, data display, parameter settings, relay type, reset methods, wiring and dimensions.
The protectors provide grounding, short circuit, phase loss, stall, current imbalance and overload protection. Working voltage is AC/DC 85 V to 265 V, and reset can be performed by key, auto-reset setting, power cycling or a 24 V±10% pulse. This manual is written in Chinese.
| Rated motor voltage | 1140 V |
|---|---|
| Motor frequency | 50 Hz, 60 Hz |
| Working voltage | AC 85-265 V, DC 85-265 V |
| Measurement accuracy | 1.0 |
| Relay contact | 1 NO contact, AC 220 V/5 A, DC 30 V/5 A |
| Short-circuit protection time | 0.3 s |
| Grounding protection time | 0.6 s |
| Phase-loss protection time | 0.6 s |
EE01 indicates a grounding fault.
The working voltage is AC 85 V to 265 V and DC 85 V to 265 V.
Apply a reset pulse with amplitude 24 V±10% to the R+ and G0 terminals.
Basic protection includes grounding, short circuit, phase loss, stall, current imbalance and overload.