Service manual for Viking Model D-2 air pressure maintenance device with installation, adjustment, and maintenance instructions.
This service manual provides detailed instructions for installing, adjusting, and maintaining the Viking Model D-2 Air Pressure Maintenance Device. It includes specifications, safety warnings, and step-by-step procedures for disassembly, part replacement, and reassembly. The device is designed to regulate air pressure in systems with continuous air supply, and the manual covers both pre-assembled and non-trim versions.
The manual also includes technical data such as pressure settings, material standards, and part numbers for components. It emphasizes safety precautions, such as relieving pressure before disassembly and ensuring proper installation between valves for isolation and maintenance access.
| Air Pressure Setting Range | 5 to 75 psi (0.34 to 5.2 bar) ±2 psi (0.14 bar) |
|---|---|
| Minimum Recommended Ambient Temperature | 40 °F (4 °C) |
| Inlet and Outlet Size | 1/4” (8 mm) tapped |
| Filter Type | Replaceable air filter |
The air pressure setting is factory set at 40 psi (2.8 bar) [inlet pressure to 175 psi (12 bar)].
Turn off the air supply, relieve pressure, loosen the lock nut, turn the adjusting screw clockwise to increase pressure or counter-clockwise to decrease pressure, then tighten the lock nut.
Materials include brass, stainless steel, neoprene, and copper, as specified in the parts list.