Viking Preaction Sprinkler System Technical Manual

This manual describes the installation, operation, and maintenance of Viking's preaction sprinkler systems.


Viking Preaction Sprinkler System Technical Manual - cover page
Brand
Viking
Category
Other
Document type
Service Manual
Language
English
Pages
64
File format
PDF
File size
4.1 MB
Published
20 October, 2023
Updated
20 October, 2023
MD5 checksum
1EF73A89AFA59F1AD935923C672536F9

About this manual

This document serves as a technical manual for Viking preaction sprinkler systems, providing instructions for installation, operation, and maintenance. It details the system description, including the use of Model E, F, G-2000P, G-3000P, and G-4000P valve assemblies, and explains how these systems meet standards such as NFPA 13.

The manual categorizes systems into Single Interlock, Double Interlock, and Non-Interlock types, each with specific release mechanisms like pneumatic, hydraulic, or electric. It further outlines system requirements, procedures for placing the system in service, inspection and testing schedules (quarterly and annual), removal from service, and comprehensive troubleshooting guides for various components and fault conditions.

What's inside

  • System Description
  • System Types and Applications
  • Single Interlock Preaction System
  • Double Interlock Preaction System
  • Non-Interlock Preaction System
  • System Requirements
  • Placing the System in Service
  • Inspections, Tests, and Maintenance
  • Removing the System from Service
  • Troubleshooting

Specifications

Valve ModelsModel E or F series deluge valve, Model G-2000P, G-3000P, or G-4000P valve assembly
Pneumatic Actuator Pressure (Low)30 PSI (2 bar)
Pneumatic Actuator Pressure (High)50 PSI (3.4 bar)
Supervisory RequirementMore than 20 sprinklers

Frequently asked questions

What are the three basic types of preaction systems defined by NFPA 13?

The three basic types are Single Interlocked, Double Interlocked, and Non-Interlocked.

What is the minimum air pressure required for a pneumatic actuator at low water pressures?

A minimum of 30 PSI (2 bar) air pressure is required for system water pressures of 175 PSI (12 bar) or less.

When should a preaction system be automatically supervised?

The system must be automatically supervised if there are more than 20 sprinklers on the system.