Troubleshooting guide for the Viessmann Vitodens 200 boiler, covering fault codes, field service solutions, programming checks, and component replacement.
This troubleshooting guide applies to the Viessmann Vitodens 200 boiler. It is intended to be used together with the Vitodens 200 Quick Start-up Guide and Start-up/Service Instructions and is not a substitute for the technical support literature supplied with the boiler and its accessories.
The guide describes a five-step process for handling customer calls: collect pertinent information, follow start-up procedures, check the programming and coding addresses, refer to the service guide supplement, and replace components only after all prior steps are completed. It also lists field service calls with suggested solutions and fault codes, including faults A1, A4, B1, F4, 06, and 07.
| Maximum boiler temperature | Modulates down approaching 75 °C / 167 °F; shuts down at 82 °C / 180 °F |
|---|---|
| Factory default differential setting | 8 °C, adjustable down to 2-3 °C / 4-5 °F |
| PPM fuse rating (models 44/60) | 0.6 Amp; if blown, replace with 0.8 Amp (Viessmann PN 9066825) |
Approximately 85% of all field issues are associated with items external to the boiler.
Air must be purged completely for at least 1 hour at start-up.
The boiler must be restarted (power ON/OFF) at least once for the changes to take effect; the control needs between 2 and 60 seconds to process and transfer data.
Set the heating curves for heating circuit A equal to B, lower the boiler factory default differential setting from 8 °C to 2-3 °C, or use a Low Loss Header.