Viessmann Vitodens200-W WB 2B Series Operating Instructions & User Information Manual
This manual contains essential safety warnings, installation requirements, and warranty information for the Vitodens200‑W WB 2B Series wall‑mounted gas‑fired condensing boiler. It emphasizes the need for qualified professional installation and regular service to prevent carbon‑monoxide hazards and ensure reliable operation.
The document explains how to start up and shut down the heating system, adjust room and domestic hot‑water temperatures, program time schedules, and use the control unit’s functions. Additional sections cover energy‑saving settings, troubleshooting indicators, and service instructions for qualified technicians.
Viessmann Vitodens 200 specifications
| Maximum boiler temperature | Modulates down approaching 75 °C / 167 °F; shuts down at 82 °C / 180 °F |
|---|---|
| Factory default differential setting | 8 °C, adjustable down to 2-3 °C / 4-5 °F |
| PPM fuse rating (models 44/60) | 0.6 Amp; if blown, replace with 0.8 Amp (Viessmann PN 9066825) |
All Viessmann Vitodens 200 documents by type
Disassembly, diagnostics and part numbers, for repair.
Day-to-day operation, settings and troubleshooting. Start here if the product is already set up.
Questions answered in these manuals
What percentage of Vitodens 200 field issues are associated with items external to the boiler?
Approximately 85% of all field issues are associated with items external to the boiler.
How long must air be purged from the water system at start-up?
Air must be purged completely for at least 1 hour at start-up.
What is the power rating of this boiler?
The boiler is available in two power ratings: 80 kW and 100 kW.
From: Viessmann Vitodens 200-W B2HA 80 and 100 kW Service Manual
What are the fuel types supported?
The boiler is designed for natural gas and liquefied gas.
From: Viessmann Vitodens 200-W B2HA 80 and 100 kW Service Manual
Who is the target audience for these instructions?
These instructions are exclusively intended for qualified contractors.
From: Viessmann Vitodens 200-W Type B2HA, B2KA Installation and Service Instructions
Can work on gas installations be carried out by anyone?
No, work on gas installations must only be carried out by a registered gas fitter.
From: Viessmann Vitodens 200-W Type B2HA, B2KA Installation and Service Instructions