Viessmann DHW Heating DHW Cylinders and Cylinder Loading Systems Technical Guide

The document describes the features and characteristics of the Viessmann DHW heating DHW cylinders and cylinder loading systems.


Viessmann DHW Heating DHW Cylinders and Cylinder Loading Systems Technical Guide - cover page
Brand
Viessmann
Category
Water heater
Document type
Other
Language
English
Pages
52
File format
PDF
File size
1.4 MB
Published
07 November, 2023
Updated
07 November, 2023
MD5 checksum
D757E68445DCB1ED92B5E63B0FDF8E29

About this manual

This technical guide from Viessmann covers DHW heating with Viessmann DHW cylinders, cylinder loading systems and freshwater modules. It presents sizing principles, product information for Vitocell cylinders and Vitotrans units, cylinder selection according to NL factor or continuous output, and sizing to DIN 4708-2 and DIN 1988-300.

It also describes cylinder loading systems using Vitocell 100-L with Vitotrans 222, connections on the DHW and heating sides, DHW circulation pipes and cylinder banks. The appendix includes questionnaires and checklists for sizing DHW cylinders and heat exchangers.

What's inside

  • Sizing systems for DHW heating
  • Product information
  • Selecting the cylinder type
  • Sizing
  • Cylinder loading systems — Vitocell 100-L with Vitotrans 222
  • Installation — DHW cylinders
  • Installation — cylinder loading system
  • Appendix
  • Keyword index

Specifications

Vitocell 100-H, type CHA capacity130, 160 and 200 l
Vitocell 300-H, type EHA capacity160, 200, 350 and 500 l
Vitocell 100-V capacity160, 200 and 300 l
Vitocell 100-V, type CVWA capacity300, 390 and 500 l
Vitocell 300-V, type EVIA-A capacity160, 200 and 300 l
Vitocell 300-V, type EVIA-A+ capacity160 and 200 l
Vitocell 300-V, type EVIA-A energy efficiency classA
Vitocell 300-V, type EVIA-A+ energy efficiency classA+
Vitocell 300-H materialStainless steel
Vitocell 300-H cylinder bank capacities700 l, 1000 l, 1500 l

Frequently asked questions

What standard is often used for sizing DHW heating systems in residential buildings?

Systems for residential buildings are often configured in accordance with DIN 4708 Part 2.

What software does Viessmann provide for sizing DHW systems?

Viessmann provides free EDIS software for reliable sizing of DHW systems.

What factors are important for hygienic operation of a DHW heating system?

Correct operating temperature, design of the DHW circulation pipe, and connection of the DHW circulation pipe to the DHW cylinder.

Can Vitocell 300-H cylinders be combined into cylinder banks?

Yes. Vitocell 300-H cylinders with 350 and 500 l capacity can be combined with on-site manifolds to form cylinder banks.