Turck IM12-DI01-2S-2R-PR/24VDC datasheet: 2-channel isolator switch amplifier for NAMUR sensors or contacts, with two relay outputs, SIL 2 and ATEX zone 2.
This four-page datasheet from Turck describes the IM12-DI01-2S-2R-PR/24VDC 2-channel isolator switch amplifier (article number 7580037). Sensors to EN 60947-5-6 (NAMUR) or potential-free contacts can be connected to the device, which may be installed in zone 2. DIP switches on the front allow selection between output mode, input current monitoring and signal doubling or single-channel operation, and the output circuit is fitted with two changeover relays.
The datasheet lists the input and output data, galvanic isolation values, display elements, mechanical data, electrical connection and environmental conditions, along with the standards applied. It also states that the device can be used in safety circuits up to SIL 2 according to IEC 61508 (a safety manual is required for such applications) and notes the WM1 resistor module plus the power bridge connectors and terminal sets available as accessories. This manual is written in Chinese.
| Article number | 7580037 |
|---|---|
| Operating voltage | 24 VDC |
| Operating voltage range UB | 10…30 VDC |
| Input channels | 2-channel or 1-channel with signal doubling |
| No-load voltage | 8.2 VDC |
| Short-circuit current | 8.2 mA |
| Relay outputs | 2 relays (single-pole double-throw contacts) |
| Switching current output | ≤ 2 A |
| Switching capacity output | ≤ 500 VA/60 W |
| Test voltage (galvanic isolation) | 2.5 kV RMS |
| Degree of protection | IP20 |
| Operating temperature | -25…+70 °C |
| Dimensions | 120 x 12.5 x 117 mm |
| Weight | 168 g |
| Terminal cross section | 0.2…2.5 mm² (AWG 24…14) |
| Mounting | DIN rail (NS35) |
| Safety rating | SIL 2 according to IEC 61508 |
Sensors compliant with EN 60947-5-6 (NAMUR) or potential-free contacts can be connected to the isolator switch amplifier.
The output circuit has two changeover relays (complementary contacts).
Yes, the device can be installed in zone 2 and is listed as ATEX for zone 2, cUL.
It can be used in safety circuits up to SIL 2 according to IEC 61508; a safety manual is required for functional safety applications.