Turck IM33-…-HI/24VDC Isolating Transducers Safety Manual

Turck IM33-…-HI/24VDC isolating transducers safety manual for safety instrumented systems up to SIL2 according to IEC 61508.


Turck IM33-…-HI/24VDC Isolating Transducers Safety Manual - cover page
Brand
TURCK
Category
Automation control Equipment
Document type
User Manual
Language
English
Pages
44
File format
PDF
File size
961 KB
Published
08 November, 2026
Updated
08 November, 2026
MD5 checksum
10E35DCF61E14A7B2021F6BDB19825A2

About this manual

This safety manual covers the use of Turck IM33-…-HI/24VDC isolating transducers in safety instrumented systems (SIS). It describes safety functions, fault types, installation, commissioning, operation, maintenance, and repair, and is based on IEC 61508 with an attached EXIDA FMEDA report.

The manual applies to device variants IM33-11EX-HI/24VDC, IM33-22EX-HI/24VDC, IM33-11-HI/24VDC, IM33-22-HI/24VDC, and IM33-12EX-HI/24VDC. These galvanically isolated transducers transmit 0/4…20 mA signals and support safety-related applications up to SIL2 with hardware fault tolerance HFT = 0.

What's inside

  • About this safety manual
  • Notes on devices
  • For your safety
  • Device specific information on safety applications
  • Installation and commissioning
  • Operation, maintenance and repair
  • Decommissioning and withdrawal from service
  • Appendix – EXIDA FMEDA Report Turck 04/07-14 R001

Specifications

Transmitter supply voltage≥ 17 V/20 mA
Output signal tolerance2 % of end value
Wire break detection threshold< 3.6 mA
Short circuit detection threshold> 21.5 mA
Safety integrity levelSIL2
Hardware fault toleranceHFT = 0

Frequently asked questions

What safety integrity level do the isolating transducers support?

The devices enable safety-related systems up to and including SIL2 according to IEC 61508.

What happens when a wire break is detected at the input?

The device switches to the safe state at an input current of < 3.6 mA and outputs a current of < 3.6 mA.

Can the second channel of dual-channel devices be used to reach a higher SIL level?

No, the second channel must not be used to increase hardware fault tolerance and achieve a higher SIL level.

Download PDF (961 KB)