Turck IM33-…-HI/24VDC isolating transducers safety manual for safety instrumented systems up to SIL2 according to IEC 61508.
This safety manual covers the use of Turck IM33-…-HI/24VDC isolating transducers in safety instrumented systems (SIS). It describes safety functions, fault types, installation, commissioning, operation, maintenance, and repair, and is based on IEC 61508 with an attached EXIDA FMEDA report.
The manual applies to device variants IM33-11EX-HI/24VDC, IM33-22EX-HI/24VDC, IM33-11-HI/24VDC, IM33-22-HI/24VDC, and IM33-12EX-HI/24VDC. These galvanically isolated transducers transmit 0/4…20 mA signals and support safety-related applications up to SIL2 with hardware fault tolerance HFT = 0.
| Transmitter supply voltage | ≥ 17 V/20 mA |
|---|---|
| Output signal tolerance | 2 % of end value |
| Wire break detection threshold | < 3.6 mA |
| Short circuit detection threshold | > 21.5 mA |
| Safety integrity level | SIL2 |
| Hardware fault tolerance | HFT = 0 |
The devices enable safety-related systems up to and including SIL2 according to IEC 61508.
The device switches to the safe state at an input current of < 3.6 mA and outputs a current of < 3.6 mA.
No, the second channel must not be used to increase hardware fault tolerance and achieve a higher SIL level.