Testo 550 A/C-Heat Pump System Troubleshooting Guide

A troubleshooting guide for the Testo 550 device covering A/C and heat pump system diagnostics, including refrigerant identification, pressure measurement…


Testo 550 A/C-Heat Pump System Troubleshooting Guide - cover page
Brand
testo
Category
Other Electronics
Document type
Service Manual
Language
English
Pages
2
File format
PDF
File size
352 KB
Published
12 November, 2026
Updated
12 November, 2026
Model
550
MD5 checksum
15386423F82F18133B29462645666A24

About this manual

This document serves as a troubleshooting guide for the Testo 550, providing instructions for diagnosing A/C and heat pump systems. It covers essential steps such as verifying airflow, identifying metering devices, and calculating design temperature differences (DTD) to determine required suction and liquid pressures.

What's inside

  • System Problem (Fixed)
  • System Problem (TXV)
  • Additional Tips
  • Refrigerant Charging
  • TXV Operation
  • Airflow Measurement

Frequently asked questions

What is the typical design evaporator DTD for 400 CFM/Ton?

The typical design evaporator DTD is -35 °.

What is the typical design condenser DTD for 10-12 SEER systems?

The typical design condenser DTD is +25°.

What is the required pressure drop across the metering device for R22 TXV systems?

A 100 psi drop is required for R22 systems.

What is the required pressure drop across the metering device for R410a TXV systems?

A 160 psi drop is required for 410a systems.