Testo 316-4 refrigerant leak detector instruction manual: exchangeable sensor heads, optical and audible gas indication, operation and technical data.
This instruction manual covers the testo 316-4, a leakage detection instrument for the fast and reliable detection of leakages on refrigeration systems and heat pumps. Gas concentrations are indicated optically and audibly, and the exchangeable sensor head lets the instrument be adapted to different refrigerants: the 0554 3180 refrigerant sensor head for R134a, R22, R404a, H2 and further CFC, HCFC and HFC refrigerants, or the 0554 3181 NH3 sensor head for ammonia. Testo states that the 316-4 is not a piece of protective equipment and must not be used as a monitoring instrument for personal safety.
The manual describes the display and control elements, charging the battery pack with the original mains unit 0554 1093, selecting the gas type, zeroing, switching between search and localization mode, and performing gas detection. It also covers maintenance such as changing and cleaning the sensor head, the meaning of the error messages Error 01 to Error 04, a table of detectable refrigerants, accessories and spare parts, and technical data including response threshold, response time, battery life, dimensions, weight, EC guideline 2014/30/EC, SAE J1627 for R134a and warranty periods. This manual is written in German.
| Sensor | Gas-sensitive semi-conductor |
|---|---|
| Reaction threshold | <3g/a / <0.1oz/yr (specified for reference refrigerants) |
| Reaction time | <1s |
| Operating conditions | -5 to 50°C / 23 to 122°F / 20 to 80%RH; limited functionality also from -20 to -5°C |
| Storage/transport conditions | -25 to 70°C / -13 to 158°F / 20 to 80%RH |
| Minimum bend radius gooseneck | 40 mm |
| Current supply | Rechargeable battery pack NiMh |
| Battery life | Approx. 6 h (at 22°C / 72°F) |
| Charging time | Approx. 8 h |
| Dimensions | 57 x 190 x 42 mm |
| Weight | 348 g |
| EC guideline | 2014/30/EC |
| Standard met | Meets SAE J1627 for refrigerant R134a |
| Warranty | Measuring instrument 24 months, sensor 12 months |
The 0554 3180 refrigerant sensor head is for R134a, R22, R404a, H2 and further CFC, HCFC and HFC refrigerants, and the 0554 3181 NH3 sensor head is for ammonia.
It indicates a non-permitted sensor head; the sensor head has to be changed.
Approx. 8 h at room temperature when the battery is completely discharged; charging is only possible between 0 and +45°C ambient temperature.
Move the sensor head as close as possible over the components at a low speed of about 3 to 5 cm per second.