Temperzone IJD Series Chilled Water Air Handling Unit Condensed Technical Data

Condensed technical data for Temperzone IJD Series belt driven chilled water air handling units, covering features, options, wiring and specifications.


Temperzone IJD Series Chilled Water Air Handling Unit Condensed Technical Data - cover page
Brand
TemperZone
Category
Other products
Document type
Product Leaflet
Language
English
Pages
2
File format
PDF
File size
24 KB
Published
10 November, 2026
Updated
10 November, 2026
MD5 checksum
142F9B01011599D57151228CBE40A019

About this manual

This condensed technical data sheet describes the Temperzone IJD Series of belt driven ducted air handling units, which form part of an air conditioning system where chilled or hot water is circulated by a central plant facility. The document covers standard features such as drain trays, rifled copper tube coils, IP55 TEFV fan motors, forward curved centrifugal fans, foil-faced closed cell foam insulation, galvanised steel cabinets and hinged access doors, plus options including EU4 filters, vertical or horizontal supply air configuration, factory-mounted electric heat elements and a polyester powder coated Tampa Tan exterior.

Typical applications named in the document include office buildings, hospitals, factory buildings, museums and airport terminals, where high static pressure and longer ductwork are considerations and the unit is sited in a separate plant room. All IJD units are right handed, with water and electrical connections on the right hand side when facing the discharge side. The sheet also lists coil and configuration ordering codes and a specification table for models IJD 370 through IJD 2400.

What's inside

  • General
  • Typical Applications
  • Standard Features
  • Options
  • Wiring
  • Order Detail
  • Summary of Choices
  • Specifications

Specifications

Nominal air flow1500–8600 l/s (IJD 370–IJD 2400)
Fan typeForward curved centrifugal, double inlet double width
Fan motor typeBelt drive, aluminium totally enclosed fan ventilated, IP55
Power source3 phase 400 V a.c. 50 Hz (342–436 V fluctuation limits)
Motor rating2.2–11 kW depending on model
Full load amps4.8–21 A depending on model
Coil test pressure2100 kPa
Heat exchange typeAluminium corrugated plate fins on expanded rifled copper tube
Coil options1, 4, 4/1, 4/E, 6, 6/1, 6/E rows or electric heat only
FinishZinc galvanised steel; optional Tampa Tan polyester powder coat
Optional electric heating12–54 kW depending on model
Optional air filterDisposable, pleated, rated EU4, 50 mm thick
Weight (4/1 row unit incl. water)180–809 kg depending on model

Frequently asked questions

On which side are the water and electrical connections on IJD units?

All temperzone IJD air handling units are right handed: when facing the discharge side of the unit, the water and electrical connections are on the right hand side.

What electrical supply does the IJD Series require?

The units require 3 phase 342–436 V a.c. 50 Hz with neutral and earth, and each unit is fully wired ready to accept the main power supply.

What type of optional filters are available for the IJD Series?

Optional filters are 50 mm thick, pleated, disposable and rated EU4.

What coil configurations can be ordered for the IJD Series?

Coil options include one row heating, four or six row cooling, four or six row cooling plus one row heating, cooling plus electric heat, or electric heat only, specified with codes such as IJD 450-4/1 H.