User manual for the SolaHD SDU AC-A Series A272-290 DIN rail UPS, covering installation, specifications, operation, diagnostics and software.
The SolaHD SDU AC-A Series A272-290 is a compact, off-line DIN rail mountable uninterruptible power supply that provides conditioned power to sensitive electronic equipment in an industrial environment. During a power outage it supplies a stepped approximation to a sine wave to simulate utility power, and its battery charges automatically when AC power is applied.
The manual covers introduction, safety instructions, installation, specifications, general description, system block diagram, operating instructions, diagnostics, battery back-up times, software and interface, and storage. It also lists included items such as the UPSMON software CD and USB cable, plus optional accessories including mounting brackets, a DIN rail clip, a dry contact relay card, and a network communication module.
| Capacity | 500 VA/300 W and 850 VA/510 W |
|---|---|
| Input voltage | 120 V +10%, -20% or 230 V +/-15% |
| Input frequency | 50 or 60 Hz, +/-10% (auto-sensing) |
| Output voltage (back-up mode) | Simulated sine wave, 120 V +/-5% or 230 V +/-5% |
| Output frequency | 50 or 60 Hz, +/-0.5% auto-sensing |
| Transfer time | Typical <8 ms |
| Battery type | Sealed, maintenance-free, lead acid |
| Recharge time | 8 hours typical |
| Overload protection | Shutdown if overload exceeds 105% at 20 s, 120% at 10 s, or 130% at 3 s; auto-recovery |
| Operating humidity | 0–95%, non-condensing |
| Audible noise | <40 dBA at 1 m |
| Dimensions | 4.87 x 11.1 x 4.81 in. (123.7 x 281.9 x 122.3 mm) |
| Safety certification | UL 1778, 5th Ed./CSA 107.3 |
The UPS ships with a user manual, UPSMON software CD, a USB cable, an SDUCOMMCVR communication slot cover, and a warning label.
Charge the battery for a minimum of 8 hours before initial use.
The typical transfer time is less than 8 ms.
It provides monitoring and diagnostic functions, including voltage, frequency and battery levels, and allows an orderly shutdown during a power failure.