Siemens SINAMICS G120X Frequency Converter Pressure Controlled Compressor Application Example

Siemens SINAMICS G120X application example for pressure controlled compressors, covering wiring, PID controller setup, cascade control, and hibernation mode.


Siemens SINAMICS G120X Frequency Converter Pressure Controlled Compressor Application Example - cover page
Brand
Siemens
Category
inverter
Document type
Application Note
Language
English
Pages
17
File format
PDF
File size
1.2 MB
Published
11 November, 2026
Updated
11 November, 2026
Model
G120X
MD5 checksum
1115695DF289C4F2CB7490B426CE3295

About this manual

This Siemens application example describes how to set up SINAMICS G120X frequency converters for pressure controlled compressor applications with up to 4 compressors. It covers single-compressor and cascade-control wiring diagrams, technological units, setpoint input, actual value sensor setting, and interconnection and tuning of the PID controller.

Additional functions described include automatic restart, cascade control basic settings, and hibernation mode. The parameterization requires minimum firmware version V 1.01, completed basic commissioning, and macro 47 “PID controller with fixed setpoint”.

What's inside

  • Introduction
  • Components used
  • Engineering
  • Parameterization description
  • Technological units
  • PID controller
  • Automatic restart
  • Cascade control
  • Hibernation Mode
  • Appendix

Specifications

Minimum firmware versionV 1.01
IOP-2 firmwareV2.3 upwards
Compressors supportedup to 4
Technological unit[bar]
Commissioning macro47

Frequently asked questions

What is the minimum firmware version for the SINAMICS G120X?

The application parameterization requires minimum firmware version V 1.01.

How many compressors does the pressure control application support?

It supports pressure controlled compressor applications with up to 4 compressors.

Which macro must be selected during basic commissioning?

Macro 47 “PID controller with fixed setpoint” must be selected.

What technological unit is used for the pressure setpoint?

The setpoint is entered in technological units, in this example [bar].