This manual provides installation, startup, maintenance, and calibration instructions for the RKI Instruments 61-1001RK-05/NC-6205-05 combustible gas detector.
This document is the Operator's Manual for the RKI Instruments 61-1001RK-05 hydrogen detector (internal amplifier type) and the NC-6205-05 hydrogen detector. It covers procedures for installing, starting up, maintaining, and calibrating the detector when used with a gas monitoring controller. The manual also includes a parts list for replacement components.
| Target Gas | Hydrogen |
|---|---|
| Area Classification | Explosion proof for Class I, Groups B, C, and D |
| Sampling Method | Diffusion |
| Detection Range | 0 to 100 %LEL |
| Response Time | 90% in 45 seconds |
| Accuracy | ± 5% of reading or ± 2% LEL |
Typical calibration frequencies are between 3 and 6 months, though this depends on usage.
Mount the detector near the ceiling or where hydrogen is most likely to accumulate.