User manual for the PowerWalker 1000/2000VA inverter, covering safety, installation, operation, specs, and troubleshooting.
This document provides safety instructions, installation steps, and operational guidelines for the PowerWalker 1000/2000VA inverter. It details how to connect and configure the unit, including battery wiring options (series, parallel, or series-parallel). The manual also covers technical specifications, such as input/output voltage ranges, efficiency, and environmental ratings. Troubleshooting is addressed with common issues and solutions.
The inverter converts DC battery power to standard AC power and includes an automatic transfer function and integrated charger. It is designed for indoor use and supports both narrow (170–280V AC) and wide (90–280V AC) input voltage modes for different load types. This manual is written in French.
| Capacity | 1000 VA/600 W or 2000 VA/1200 W |
|---|---|
| Input Voltage Range (AC) | 90~280V AC |
| Output Voltage | 230V AC +10/-18% |
| Output Frequency | 50/60Hz ±0.5Hz |
| Efficiency (AC to AC) | > 95% |
| Battery Voltage | 12V CC or 24V CC |
| Charger Voltage | 13.7V ±0.2V or 27.4V ±0.4V |
| Charger Current | 10A max |
| Transfer Time | 15-20ms, up to 40ms |
| Dimensions (mm) | 255x80x224 |
| Weight | 2.3kg or 2.5kg |
| Operating Temperature | 0 ~ 40°C |
The transfer time is typically 15–20ms, with a maximum of 40ms.
The battery must be connected to provide a 12V DC input for the 1000VA model.
The battery must be connected to provide a 24V DC input for the 2000VA model.
The battery must be recharged for at least 8 hours to resolve the low voltage issue.