User manual for the PMV D30 Compact digital positioner, covering installation, operation, maintenance, troubleshooting, technical data, and spare parts.
The PMV D30 is a digital positioner primarily designed for controlling modulating valves. It can be used with single- or double-acting actuators, whether rotary or linear, and can be fitted with limit switch contacts, pressure gauges, and pressure sensors for diagnostics. Modules can be assembled at the factory or installed later.
This French-language user manual covers storage, installation, control, maintenance, troubleshooting, technical data, dimensions, and spare parts. It includes safety warnings for the intrinsically safe version, instructions for air supply and tubing, mounting details, and electrical and pneumatic connections. This manual is written in French.
| Air supply pressure | 1.4–8 barg (20–115 psi) |
|---|---|
| Air quality standard | DIN/ISO 8573-1-2001 3.2.3 |
| Filtration | 5 microns |
| Dew point | -40 °C/F |
| Oil content | 1 mg/m³ (0.83 ppm by weight) |
| Recommended tubing inside diameter | Minimum Ø 6 mm (¼ in.) |
| Mounting interface | ISO F05 |
| Pneumatic connections | ¼ in. NPT or G ¼ in. |
| Electrical connections | M20 x 1.5 or NPT ½ in. |
It can be used with single- or double-acting actuators, whether rotary or linear.
The air supply must be provided at 1.4–8 barg (20–115 psi).
Tubing with a minimum internal diameter of Ø 6 mm (¼ in.) is recommended.
The cover screws should be tightened to 1.5 Nm, ±15%.