PMV 14321-99.6 P-1500/P-1700 Manual

This document is a manual for the P-1500 and P-1700 series. It confirms that these appliances comply with applicable standards and are intended for installation in a machine/application. It also emphasizes that commissioning is strictly prohibited until evidence is provided that the machine/application is also in compliance with EC directive 89/392/EEC.


PMV 14321-99.6 P-1500/P-1700 Manual - cover page
Brand
PMV
Category
Industrial Robot
Document type
User Manual
Language
English
Pages
12
File format
PDF
File size
204 KB
Published
04 January, 2023
Updated
27 September, 2023
MD5 checksum
1CFFE77294416C22A9EEC31827D19934

About this manual

This document serves as a user manual for the PMV P-1500, P-1520, P-1700, P-1710, P-1720, and P-1730 series positioners. It provides essential guidance on the proper storage and handling of these precision instruments to prevent damage, including specific requirements for warehouse and field storage conditions.

The manual details the operating principle based on balanced forces and provides step-by-step instructions for key maintenance and setup tasks. These include zeroing the positioner, adjusting the control pressure range to increase or decrease actuator travel, changing the valve action, and cleaning the valve body components.

What's inside

  • Manufacturers declaration
  • Storage and handling procedures
  • Function
  • Zeroing the positioner
  • Air preparation
  • Adjusting the Control Pressure Range
  • Changing the action
  • Cleaning the valve body

Specifications

Supply pressureup to 10 bar (150 psi)
Air quality requirementdry, clean oil free air
Filter micron rating25 microns

Frequently asked questions

What are the storage requirements for PMV positioners?

Units should be stored in original shipping containers in a clean, cool (15-26 °C), and dry area out of direct sunlight.

How do I adjust the control pressure range?

To increase travel, back off the locking screw and turn the spring clockwise. To reduce travel, turn the spring and top spring guide clockwise.

What air quality is required for operation?

The positioner must be fed with dry, clean oil-free air, typically using a 25-micron filter.

Download PDF (204 KB)