User manual for the Phoenix Guardian HEPA System, covering installation, operation, maintenance, and safety for air quality remediation in restoration projects.
This manual provides step-by-step instructions for installing, operating, and maintaining the Phoenix Guardian HEPA System. It details ducting options, airflow controls, electrical requirements, and safety precautions. The system is designed for indoor use in restoration projects to filter airborne particles and manage air pressure. Maintenance sections cover filter replacement and airflow checks, while service information includes warranty and motor replacement procedures.
The unit features 2-speed operation (1400-900 CFM), multiple ducting options, a built-in manometer, and a wheeled cart design. It includes filters for particle capture and optional chemical odor removal. Safety warnings address electrical use, positioning, and filter maintenance to prevent motor overload or exposure to high voltage.
| Power | 12 amps, 110-120 VAC, Grounded |
|---|---|
| Blower Speeds | 2-Speed High: 1400 CFM* w/o external duct, Low: 900 CFM* w/o external duct |
| Duct Connections | Inlet: 18” flex duct or 12” adapter; Outlet: 10.5” square with collars for lay-flat duct or 12” adapter |
| Filters | 24” x 24” 1-stage 1” Spun Polyester, 2-stage 2” Pleated Media, 3-stage 12” V-bank HEPA (optional), 4-stage 2” Carbon and Potassium Permanganate |
| Dimensions | Shipping Width 25”-29”, Height 39”-45”, Depth 25”-28”, Weight 121 Lbs-155 Lbs |
The unit has a true 1400 cfm capacity, which can clean one air change of a 12 x 14 foot room in less than a minute.
It must always be used in the upright position, with the air inlet on top and the front outlet at least 1 foot from walls and obstructions.