Omega user guide for SSRDC100V, SSR330, SSR660, SSRINT660, SSR3PH660 and SSRDIN660 series solid state relays, covering precautions, specs, wiring and derating.
The OMEGA Solid State Relays are normally open, solid state switching devices with no moving parts. The guide states that they are designed to control 120 V, 240 V, 440 V, or 660 V alternating current and provide zero voltage switching and 4000 VAC isolation between the load terminals and the control signal.
The document covers installation precautions, finned heat sinks, fuse protection, leakage current, model tables, schematics, mechanical drawings, wiring examples, and derating curves. It also lists accessory fuses, fuse blocks, thermal compound, and heat sinks.
| Isolation voltage | 4000 VAC |
|---|---|
| Contact configuration | Normally open |
| Switching method | Zero voltage switching |
| Leakage current in OFF state | Typically 5 to 15 mA |
| Operating life | Tens of millions of cycles |
| SSRDC100VDC8 load voltage range | 0-100 Vdc |
| SSRDC100VDC40 load current | 40 A DC |
| SSR330DC10 control voltage | 4 Vdc minimum; 32 Vdc maximum |
| SSR330DC10 load voltage range | 24 to 330 Vac |
The SSR330DC10 has a load voltage range of 24 to 330 Vac.
All SSRs have a typical leakage current of 5 to 15 mA in the OFF state.
Yes. Panel-mount SSRs must be mounted on a Finned Heat Sink or on a metal plate of adequate size.
Select a fuse with a current and voltage rating less than the maximum rating of the relay.