Nexans H07Z1-U/H07Z1-R Cca TYPE 2 Cable Identification and Installation Guide

This manual provides cable identification codes, symbols, abbreviations, correction factors, and maximum cable length tables for Nexans H07Z1-U/R cables.


Nexans H07Z1-U/H07Z1-R Cca TYPE 2 Cable Identification and Installation Guide - cover page
Brand
Nexans
Category
Other Electronics
Document type
User Manual
Language
Dutch
Pages
82
File format
PDF
File size
6.9 MB
Published
27 October, 2026
Updated
27 October, 2026
MD5 checksum
167A82B2CA8A5D582D2C5043B72663FD

About this manual

This document serves as a technical guide (N-manual) for the installation of Nexans ALSECURE® H07Z1-U/H07Z1-R Cca TYPE 2 cables. It details conductor identification according to HD308S2 standards, explaining color codes and numbering conventions for fixed or mobile installations.

The manual includes comprehensive tables showing maximum cable lengths based on current load and voltage drop (4%), along with necessary correction factors for various installation conditions such as open air, underground burial, proximity to other cables, and specific ambient temperatures. This manual is written in Dutch.

What's inside

  • Identification of conductors
  • Used symbols and abbreviations
  • Notes on mentioned values
  • Correction factors
  • Maximum cable length at 12 V DC
  • ALSECURE H07Z1-U/H07Z1-R specifications
  • H07V-U /H07V-R Eca (VOB)
  • LINEAX H07RN-F Eca

Specifications

Standard for conductor identificationHD308S2
Maximum voltage drop limit4%
Power factor for calculations (cos phi)0.8
Ambient temperature for open air installation30°C
Burial depth for underground installation70 cm

Frequently asked questions

What standard is used for conductor identification?

The document uses the HD308S2 standard for identifying conductors in fixed or mobile installations.

What is the maximum allowed voltage drop?

The tables are calculated to ensure the voltage drop does not exceed 4%.