Leonard TM-28 Thermostatic Water Mixing Valve Installation and Service Manual

Installation, adjustment and service instructions for the Leonard TM-28 thermostatic water mixing valve, with high-limit stop reset, troubleshooting and parts.


Leonard TM-28 Thermostatic Water Mixing Valve Installation and Service Manual - cover page
Brand
Leonard
Category
Other
Document type
Service Manual
Language
English
Pages
6
File format
PDF
File size
108 KB
Published
17 November, 2026
Updated
17 November, 2026
MD5 checksum
90F08314C57BB2434ECDD8B7FDAF7CD0

About this manual

Bulletin G-28 from Leonard Valve Company covers the Type TM-28 thermostatic water mixing valve. It gives installation requirements, including connecting the hot and cold supplies, installing union angle strainer checkstops on both supply lines and a shutoff valve on the outlet pipe, and it states a maximum operating pressure of 125 PSI (860 kPa).

The document explains how to reset the adjustable high temperature limit stop, troubleshoot problems with packings, the port sleeve assembly, the thermostat group and the checkstops, and dismantle and clean the valve. It also shows required piping methods for recirculated hot water systems, a parts breakdown with repair kits, notes on flow capacities and a one-year limited warranty.

What's inside

  • Installation
  • Adjustment and Service
  • To Reset Adjustable High Temperature Limit Stop
  • Troubleshooting Instructions
  • Required Methods of Piping (Recirculated Hot Water Systems)
  • Instructions for Dismantling Valve
  • Valve Parts, Checkstop Parts and Repair Kits
  • Flow Capacities
  • Limited Warranty

Specifications

Maximum Operating Pressure125 PSI (860 kPa)
High Temperature Limit Stop factory settingApproximately 120°F (49°C)
Minimum flow when setting up a recirculated system1 GPM

Frequently asked questions

What is the maximum operating pressure of the Leonard TM-28 valve?

The maximum operating pressure is 125 PSI (860 kPa).

What temperature is the high temperature limit stop set to at the factory?

It is set at approximately 120°F (49°C) with an incoming hot water supply temperature of 150°F (65°C).

What must the installer do if the incoming hot water is higher than 150°F (65°C)?

The high temperature limit stop must be reset by the installer, since the valve would otherwise deliver water above 120°F (49°C) at full hot.

What parts kit is required for a leak at the pointer rod?

Kit #1/28 (Packings & Gaskets) is listed for a leak at the pointer rod and a leak between the valve cover and base.