Installation, adjustment and service instructions for the Leonard TM-28 thermostatic water mixing valve, with high-limit stop reset, troubleshooting and parts.
Bulletin G-28 from Leonard Valve Company covers the Type TM-28 thermostatic water mixing valve. It gives installation requirements, including connecting the hot and cold supplies, installing union angle strainer checkstops on both supply lines and a shutoff valve on the outlet pipe, and it states a maximum operating pressure of 125 PSI (860 kPa).
The document explains how to reset the adjustable high temperature limit stop, troubleshoot problems with packings, the port sleeve assembly, the thermostat group and the checkstops, and dismantle and clean the valve. It also shows required piping methods for recirculated hot water systems, a parts breakdown with repair kits, notes on flow capacities and a one-year limited warranty.
| Maximum Operating Pressure | 125 PSI (860 kPa) |
|---|---|
| High Temperature Limit Stop factory setting | Approximately 120°F (49°C) |
| Minimum flow when setting up a recirculated system | 1 GPM |
The maximum operating pressure is 125 PSI (860 kPa).
It is set at approximately 120°F (49°C) with an incoming hot water supply temperature of 150°F (65°C).
The high temperature limit stop must be reset by the installer, since the valve would otherwise deliver water above 120°F (49°C) at full hot.
Kit #1/28 (Packings & Gaskets) is listed for a leak at the pointer rod and a leak between the valve cover and base.