This document describes the installation, adjustment and maintenance instructions for the Leonard valve models TM-26 and TM-26-LF.
This bulletin covers installation, adjustment, service, piping methods, troubleshooting and parts for Leonard TM-26 and TM-26-LF thermostatic water mixing valves. It states a maximum operating pressure of 125 PSI (860 kPa) for hot and cold water and describes resetting the adjustable high temperature limit stop.
The document includes required piping methods for recirculated hot water systems, dismantling and cleaning instructions, and parts breakdowns with repair kits. It also notes that the valve must be cleaned and maintained regularly.
| Maximum operating pressure | 125 PSI (860 kPa) for hot and cold water |
|---|---|
| Factory high temperature limit stop | Approximately 120°F (49°C) with 150°F (65.5°C) incoming hot water |
The maximum operating pressure is 125 PSI (860 kPa) for hot and cold water.
It is factory set at approximately 120°F (49°C) with an incoming hot water supply temperature of 150°F (65.5°C).
The high temperature limit stop must be reset by the installer.
The valve must be piped according to Leonard Required Piping Method #2.