KIMO CP 300 Pressure Transmitter Technical Data Sheet

Technical data sheet for the KIMO CP 300 pressure transmitter with interchangeable SPI sensor, configurable ranges, dual outputs, and optional Modbus.


KIMO CP 300 Pressure Transmitter Technical Data Sheet - cover page
Brand
KIMO
Category
Automation control Equipment
Document type
Datasheet
Language
English
Pages
4
File format
PDF
File size
843 KB
Published
17 November, 2026
Updated
17 November, 2026
MD5 checksum
229D016BFF266C38D5629420C670EBEA

About this manual

The KIMO CP 300 is a pressure transmitter with an interchangeable SPI sensor, offering measuring ranges from 10 Pa to 10,000 Pa. It features configurable intermediate and centre zero ranges, optional air velocity and airflow functions, and simultaneous display of up to four parameters.

The device provides two analogue outputs (4-20 mA or 0-10 V), RS232, RS485 Modbus (optional), two relays, visual and audible alarms, and self-calibration via an internal electro-valve. Housings are available in ABS or aluminum with IP65 protection.

What's inside

  • Transmitter features
  • Housing features
  • Functions
  • Air velocity and airflow functions
  • Configurable intermediate and centre zero ranges
  • Integration of pressure measurement
  • Measurement and temperature compensation
  • Relays and Alarms
  • Self calibration
  • Technical Specifications

Specifications

Measuring range0/+10 Pa to -10,000/+10,000 Pa (model dependent)
Power supply24 Vac/Vdc, 115 Vac, or 230 Vac ±10%
Output signals2 × 4-20 mA or 2 × 0-10 V (4 wires)
Accuracy±0.5% of reading ±1 Pa (SPI-100/500/1000)
Resolution1 Pa (0.1 Pa on CP 301 optional)
Housing materialABS or ALU
Protection classIP65
Operating temperature0 to +50 °C

Frequently asked questions

What measuring ranges are available for the CP 300 pressure transmitter?

The CP 300 offers ranges from 0/+10 Pa up to -10,000/+10,000 Pa depending on the model.

What output signals does the CP 300 support?

It provides two analogue outputs selectable between 4-20 mA and 0-10 V.

How does the self-calibration function work?

An internal electro-valve automatically adjusts the zero point at configurable intervals to eliminate drift.