Design charts for Keystone Valera™ Series retaining wall units, showing height limits and soil reinforcement requirements.
This document provides design charts for Keystone Valera™ Series retaining wall units, including gravity and reinforced wall height limits based on soil type and reinforcement level. It includes charts for sand/gravel, silty sand, and silt/lean clay soils, with height limits for different backslope ratios. Reinforced wall charts specify geogrid reinforcement requirements and design heights for various soil conditions. All charts assume standard soil properties and compaction levels, with notes that final designs must be prepared by a licensed professional engineer.
| Maximum Gravity Wall Height for Sand/Gravel | 2.67' for 4H:1V, 2.00' for 3H:1V |
|---|---|
| Minimum Wall Embedment for Reinforced Walls | 6 inches or 10% of height |
| Geogrid LTDS Minimum | 1800 plf |
The maximum height is 2.67 feet.
It is 6 inches or 10% of the wall height, depending on slope conditions.
It is 1800 plf.