Help manual for the Kepware Philips P8/PC20 driver, covering device setup, data types, addressing, and error messages for OPC client connections.
The Philips P8/PC20 Driver is a Kepware driver help document for connecting Philips P8 and PC20 devices to OPC client applications such as HMI, SCADA, Historian, MES, ERP, and custom applications. It covers device setup, modem setup, supported data types, address descriptions for PC20 and P8 devices, and error descriptions. The document notes that a Philips P8 device is byte-oriented and always uses an offset in words even when the requested data type is smaller, while a Philips PC20 device is nibble-oriented and uses only the least significant nibble of a byte to store its data.
Device setup lists supported devices including PC20 using the CI21 or VI21 card, MC30 using the CI30 card, and MC31, MC41, ISCOS10, ISCOS60, and ISCOS70. It identifies PPCCOM as the communication protocol and lists baud rates of 9600 and 19200, even parity, 8 data bits, and 1 or 2 stop bits. Device IDs range from 0 to 15, allowing up to 16 PLCs on a network. The address sections describe PC20 syntax PAAA D N(N) and IEC 1131-compliant P8 addressing for discrete inputs, discrete outputs, and memory areas, with data ranges and access types.
| Supported Devices | PC20, MC30, MC31, MC41, ISCOS10, ISCOS60, ISCOS70 |
|---|---|
| Communication Protocol | Philips Programmable Controller Communication Protocol (PPCCOM) |
| Baud Rate | 9600, 19200 |
| Parity | Even |
| Data Bits | 8 |
| Stop Bits | 1 or 2 |
| Device ID Range | 0 to 15 |
| Maximum PLCs per Network | 16 |
| PC20 Address Syntax | PAAA D N(N) |
The driver supports PC20, MC30, MC31, MC41, ISCOS10, ISCOS60, and ISCOS70 devices.
It uses the Philips Programmable Controller Communication Protocol, or PPCCOM.
The listed settings are 9600 or 19200 baud, even parity, 8 data bits, and 1 or 2 stop bits.
Device IDs can range from 0 to 15.