About this manual

This document provides installation instructions for the I/A Series Model IMT25 Intelligent Magnetic Flow Transmitter. It details procedures for mounting the transmitter to surfaces or pipes (IMT25-S/P) or directly onto specific flowtube models, including 8000A wafer body and various flanged series. The guide covers hardware switch settings for power sources and output configurations.

What's inside

  • Introduction
  • Transmitter Mounting Procedures
  • Wire Entrances and Conduit Connections
  • Wiring a Remotely Mounted Transmitter
  • Transmitter I/O Wiring
  • Installing Fieldbus Software

Frequently asked questions

What fluids is the IMT25 flowmeter designed to measure?

The flowmeter is designed for use with most conductive fluids, ranging from common to very difficult-to-handle types.

What is the maximum ambient temperature limit for an integrally mounted IMT25 transmitter?

The ambient limit for an integrally mounted transmitter must not exceed 70°C (158°F).

What is the maximum load resistance for a 4 to 20 mA output circuit using external power?

The maximum load resistance is 1950 Ω when using external power.