HZK HSM6E Series Electronic Molded Case Circuit Breaker User Manual

User manual for HZK HSM6E series electronic molded case circuit breakers covering installation, dimensions, protection settings, and maintenance.


HZK HSM6E Series Electronic Molded Case Circuit Breaker User Manual - cover page
Brand
HZK
Category
Switch disconnector
Document type
User Manual
Language
Chinese
Pages
22
File format
PDF
File size
1.7 MB
Published
07 November, 2026
Updated
07 November, 2026
MD5 checksum
13C54547EB8D17B578960F4560592846

About this manual

The HZK HSM6E series electronic molded case circuit breakers are designed for AC 50 Hz systems with rated insulation voltage 1000 V, rated operational voltage up to 690 V, and rated currents from 32 A to 1600 A. They provide overload long-time delay, short-circuit short-time delay, short-circuit instantaneous, and ground-fault protection with adjustable current and time settings, plus a magnetic instantaneous backup trip. The breakers comply with IEC 60947-2 and GB/T 14048.2 standards and are suitable for altitudes up to 2000 m, ambient temperatures -5 °C to +40 °C, pollution degree 3, and installation category III.

The manual details installation requirements including busbar/cable cross-sections, tightening torques, safety clearances, altitude and temperature derating factors, and outline/drilling dimensions for front, rear, plug-in, and draw-out connections for each frame size (100, 250, 400, 800, 1600). It also covers accessory wiring (undervoltage release, shunt release, motor operator, alarm and auxiliary contacts), protection parameter adjustment, and routine inspection, testing, and maintenance procedures. This manual is written in Chinese.

What's inside

  • Purpose and scope
  • Installation (busbar/cable selection, safety distances, tightening torque, altitude derating, temperature derating)
  • Outline and installation dimensions (front connection, rear connection, plug-in front/rear, draw-out)
  • Accessory installation and wiring (rotary handle, motor operator, undervoltage/shunt releases, alarm/auxiliary contacts)
  • Protection parameter setting and modification
  • Installation, use, maintenance, and repair

Specifications

Rated insulation voltage1000 V
Rated operational voltage690 V AC
Rated frequency50 Hz
Rated current range32 A to 1600 A
Standards complianceIEC 60947-2, GB/T 14048.2
Protection functionsOverload long-time delay, short-circuit short-time delay, short-circuit instantaneous, ground fault
Backup magnetic instantaneous tripYes
Isolation functionYes
Maximum altitude2000 m
Ambient temperature range-5 °C to +40 °C
Pollution degree3
Installation categoryIII
Mounting orientationVertical or horizontal

Frequently asked questions

What is the rated current range of the HSM6E series?

The HSM6E series covers rated currents from 32 A up to 1600 A.

Which standards does the HSM6E circuit breaker comply with?

It complies with IEC 60947-2 and GB/T 14048.2.

What are the installation safety clearances for the HSM6E-400 model?

For HSM6E-400, the safety distances are L=100 mm, A=25 mm, B=25 mm, C=80 mm.

How are the protection parameters set on the HSM6E breaker?

Protection parameters (Ir1, t1, Ir2, t2, Ir3, Ir4, t4) are preset at the factory and can be adjusted on-site using the adjustment knobs if necessary.

Download PDF (1.7 MB)