Hochiki ASB digital analog sounder base for use with Hochiki sensors, providing audible alarms via SLC with programmable evacuation codes and 85dB SPL.
The Hochiki ASB is a digital analog sounder base designed to work with Hochiki sensors like ALG-V and ATG-EA. It connects via Hochiki’s DCP SLC circuit and provides local audible alarms. It supports programmable evacuation codes including continuous, march, and ANSI temporal patterns. The base learns sensor addresses and operates within a 127-device loop. It has a high sound pressure level of 85dB at 10 feet and is suitable for hotels, apartments, and hospitals.
The ASB is powered by 17–41VDC and can be configured for different output patterns across 16 states. It also supports auxiliary power and has environmental ratings for operation from 0°C to 50°C. Wiring diagrams and loop limits are provided for installation.
| Operating Voltage | 17 ~ 41 VDC |
|---|---|
| SLC Current Consumption | 110µA (Typical) 110µA (Alarm) |
| Sound Pressure Level at 10ft | 85dB Max. |
| Quantity Per Loop | 127 |
| Operating Temperature Range | 32°F (0°C) ~ 122°F (50°C) |
| Dimensions (without sensor) | 1.34”H x 5.94”D |
| Weight | 0.455 lb |
The ASB is compatible with Hochiki sensors ALG-V, ALK-V, ACA-V, AIE-EA, and ATG-EA.
The ASB provides a maximum sound pressure level of 85dB at 10 feet.
Up to 127 sensors and 127 ASBs can be used on one SLC loop.
The ASB operates from 32°F (0°C) to 122°F (50°C).