User manual for the Hezhong Electric HZZB-II transformer turns ratio and group tester, covering features, specifications, operation, precautions, and…
The HZZB-II is an automatic transformer turns ratio and group tester made by Hezhong Electric for power industry departments. It measures turns ratio and connection group in one operation and provides automatic group conversion, phase-sequence switching, range switching, calibration, relative-error calculation, automatic test-voltage cutoff, and storage of up to 30 measurements.
The manual describes wiring and menu operation, standard-ratio and tap-ratio settings, history data review, printing, precautions, and the product list. Its stated specifications include a 1 to 10000 turns-ratio range, groups 1 to 12, accuracy of 0.2 class for 1-1000 and 0.5 class for 1000-10000, AC 220 V ±10% at 50 Hz power, -5°C to 40°C operating temperature, humidity below 85%, dimensions of 400 × 335 × 185 mm, and a weight of 8 kg. This manual is written in Chinese.
| Turns ratio measurement range | 1 to 10000 |
|---|---|
| Group | 1 to 12 points |
| Accuracy | 0.2 class for 1-1000; 0.5 class for 1000-10000 |
| Power supply | AC 220 V ±10%, 50 Hz |
| Operating temperature | -5°C to 40°C |
| Operating humidity | Less than 85% |
| Dimensions | 400 × 335 × 185 mm |
| Power fuse | 2 A |
| Test fuse | 0.5 A |
| Stored measurements | Up to 30 |
The turns ratio measurement range is 1 to 10000.
It automatically saves measurements and stores up to 30.
Turn off the instrument, replace the fuse with one of the same rating, and retest.
No. The transformer neutral point is not connected to the instrument or ground.