Hailin T51 Series Electric Thermal Actuator Technical Specifications and User Manual

Hailin T51 series electric thermal actuator technical specifications and instructions for HVAC valve control.


Hailin T51 Series Electric Thermal Actuator Technical Specifications and User Manual - cover page
Brand
Hailin
Category
Industrial Supply
Document type
User Manual
Language
Chinese
Pages
2
File format
PDF
File size
420 KB
Published
16 November, 2026
Updated
16 November, 2026
MD5 checksum
95F99CBE2F81B30DB6E3520BE5426AAA

About this manual

Hailin T51 series electric thermal actuators are heat-actuated switching valve actuators used to open or close heating or cooling system pipes for room temperature control. They mount on hot or cold water valves and use a thermal (electric wax) structure to control valve position.

The document covers product features, working principle, initial opening function, stroke indication, split installation, model variants, technical specifications, characteristic curves, and installation and wiring instructions. This manual is written in Chinese.

What's inside

  • Overview
  • Product Features
  • Application
  • Working Principle
  • Initial Opening Function
  • Stroke Indication
  • Split Installation
  • Product Models
  • Technical Specifications
  • Installation and Wiring

Specifications

Voltage (T51V220)AC220V±10%
Voltage (T51V24)AC24V±10%
Peak current (T51V220)300mA
Peak current (T51V24)250mA
Power consumption2W
Running timeabout 3 minutes
Stroke4mm
Torque100N±5%
Fluid temperature0-100°C
Ambient temperature0-60°C
Protection ratingIP54
CE standardEN60730
Housing / colorNylon / gray
Weight100g
Cable2 x 0.75mm PVC, gray / 1 m
Wire cross-section1.5mm

Frequently asked questions

What is the initial opening function of the normally closed actuator?

For normally closed units, the initial state stays open to ease installation; after the first power-on for about 6 minutes, it automatically ends and the actuator remains normally closed.

How should the actuator be installed on the valve?

The adapter is first installed on the valve, then the actuator is fixed to the adapter by hand without tools.

Which installation orientations are recommended?

Vertical or horizontal installation is recommended; downward installation is not recommended because it reduces valve service life.

What protection rating does the actuator have?

The actuator has an IP54 protection rating.

Download PDF (420 KB)