Product manual for the Hailin PQF Series automatic air vent valve used in refrigeration and heating systems.
The Hailin PQF Series automatic air vent valve is installed at high points in refrigeration or heating systems to discharge accumulated gas. The manual covers its application environment, features, technical parameters, structure and dimensions, installation and commissioning, and maintenance.
It is suitable for air-conditioning refrigeration, independent heating, district heating, and radiant floor heating systems. Features include fast automatic air discharge, high sensitivity, reliability, water-gas separation design, reduced system noise, and online cleaning of the valve core. This manual is written in Chinese.
| Standard | GB/T8464-2008, threaded iron and copper valves |
|---|---|
| Nominal diameter | DN15 to DN25 |
| Nominal pressure | PN16 |
| Medium | Water and ethylene glycol solution up to 60% |
| Medium temperature | -10 to 120 C (liquid) |
| Body and cap material | Brass |
| O-ring material | EPDM |
| Width A | 47 mm (DN15, DN20, DN25) |
| Height H | 72 mm (DN15, DN20, DN25) |
| Connection thread | G 1/2 (DN15), G 3/4 (DN20), G 1 (DN25) |
Air-conditioning refrigeration, independent heating, district heating, and radiant floor heating systems.
-10 to 120 degrees C in liquid state.
It must be installed vertically at the highest point of the pipe; do not install it upside down or continue applying torque after tightening.
Once a year is recommended; more often where water quality is poor or scaling is likely.