CSA hazardous area approval information and safe-use installation instructions for the Fisher FIELDVUE DLC3020f digital level controller on FOUNDATION Fieldbus.
This instruction manual supplement (D104408X012, April 2022) covers CSA hazardous area approvals for the Fisher FIELDVUE DLC3020f Digital Level Controller used on FOUNDATION Fieldbus. It lists approval information and notes that no special conditions for safe use apply to the intrinsically safe, explosion-proof, Division 2 and dust ignition-proof approvals; users should refer to Table 1 and the product nameplate for the applicable certification.
The document gives entity and FISCO parameters for the RTD and main circuit terminals, includes CSA schematic drawing GE37118 and related notes, and states installation requirements such as the Canadian Electrical Code (CEC) Part 1 and ANSI/ISA RP12.6. It also lists grounding, maximum safe-area voltage, barrier connection and cable parameter requirements.
| Intrinsically Safe Rating | Class I, II, III Division 1 Groups A,B,C,D,E,F,G; T4 |
|---|---|
| Explosion-proof Rating | Class I Division 1 Groups B,C,D; T6 |
| Dust Ignition-proof Rating | Class II Division 1,2 Groups E,F,G; T6 |
| RTD Terminals (Entity) | Voc = 6.6 VDC; Isc = 29.5 mA; Po = 49 mW; Ca = 22 µF; La = 40 mH |
| Main Circuit Terminals (Entity) | Vmax = 24 VDC; Imax = 380 mA; Pi = 1.4 W; Ci = 5 nF; Li = 0.55 mH |
| Main Circuit Terminals (FISCO) | Vmax = 17.5 VDC; Imax = 380 mA; Pi = 5.32 W; Ci = 5 nF; Li = 0 mH |
| Maximum Safe Area Voltage | 250 Vrms maximum |
| Intrinsically Safe Ground Resistance | Less than one ohm |
| Cable Loop Resistance | 15 to 150 ohms/km |
| Cable Inductance per Unit Length | 0.4 to 1 mH/km |
| Cable Capacitance per Unit Length | 80 to 200 nF/km |
No. The document states that for intrinsically safe, explosion-proof, Division 2 and dust ignition-proof approvals there are no special conditions for safe use; refer to Table 1 and the nameplate.
Voc = 6.6 VDC, Isc = 29.5 mA, Po = 49 mW, Ca = 22 µF, and La = 40 mH.
Maximum safe-area voltage should not exceed 250 Vrms.
Installation must follow the Canadian Electrical Code (CEC) Part 1 and ANSI/ISA RP12.6.