Fisher CAV4 Control Valve Instruction Manual

Instruction manual for the Fisher CAV4 control valve and Cavitrol IV trim, covering installation, maintenance, and parts ordering.


Fisher CAV4 Control Valve Instruction Manual - cover page
Brand
Fisher
Category
Other
Document type
Service Manual
Language
English
Pages
32
File format
PDF
File size
422 KB
Published
23 November, 2026
Updated
23 November, 2026
MD5 checksum
0C984504BBD40DCF19661EDEE46D0831

About this manual

The Fisher CAV4 control valve is an angle or globe (NPS 2 only) valve with soft metal-to-metal seats, Cavitrol IV trim, cage guiding, and push-down-to-close valve plug action. This instruction manual covers installation, maintenance, and parts ordering for the valve and Cavitrol IV trim, including information on flushing trim.

Specifications include available configurations, end connection styles, shutoff classifications, flow direction, flow characteristic, and approximate weights. Maintenance topics include packing lubrication and replacement, trim removal and replacement, and use of optional flushing trim.

What's inside

  • Introduction
  • Specifications
  • Installation
  • Principle of Operation
  • Maintenance
  • Packing Maintenance
  • Trim Removal
  • Trim Replacement
  • Parts Ordering
  • Parts List

Specifications

Body typeAngle or globe (NPS 2 only)
TrimCavitrol IV trim
SeatsSoft metal-to-metal seats
Flow characteristicLinear
Flow direction, angle bodiesIn through side connection, out bottom connection
Flow direction, globe bodiesFlow down
End connectionsButtwelding ends; raised-face or ring-type joint flanged ends
Maximum inlet pressure, temperature, and pressure dropsConsistent with ASME B16.34 CL1500 and CL2500 ratings
Shutoff classificationTSO (tight shutoff) trim

Frequently asked questions

What does this manual cover?

It covers installation, maintenance, and parts ordering information for the Fisher CAV4 control valve and Cavitrol IV trim, including flushing trim information.

What is Cavitrol IV trim commonly used for?

It is most often used to help eliminate cavitation damage on liquid service where the differential pressure drop is greater than 207 bar (3000 psi).

How does liquid flow through the valve?

Liquid enters through the side connection, undergoes four staged pressure drops, and leaves through the bottom connection.

How can earlier soft metal-to-metal seated valves be identified?

By the letters SMS stamped on the seat ring or lower cage assembly.