eGate Flex-T-RH / Flex-Sky-nSens Modular Wireless Transmitters Manual

Manual for the eGate Flex-T-RH and Flex-Sky-nSens modular wireless transmitters, covering installation, wiring, configuration, and use with eGate Sky devices.


eGate Flex-T-RH / Flex-Sky-nSens Modular Wireless Transmitters Manual - cover page
Brand
E GATE
Category
Automation control Equipment
Document type
User Manual
Language
English
Pages
9
File format
PDF
File size
312 KB
Published
16 November, 2026
Updated
16 November, 2026
MD5 checksum
9FEB6BA479DB149751FFBA1B00FDCE62

About this manual

This manual describes the eGate-Flex-T-RH and eGate-Flex-Sky-nSens modular wireless transmitters from eGate Smart Building Innovation. The devices consist of a measurement module and a radio module: the T-RH module measures ambient temperature and relative humidity, while the nSens module accepts an external eGate-nSens humidity and temperature probe. The manual covers opening the measurement module, wiring, configuration, and mounting.

Configuration is done with a Nokeval DCS772 programming cable and the Nokeval Mekuwin software (Protocol SCL, Baud 9600, Address 0), with settings stored in the EEPROM of the measurement and radio modules. With the Flex-Sky-Radio module, the transmitter uses Semtech LoRa modulation with the Nokeval NLORA1 protocol to send measurement data to a compatible gateway or receiver such as the eGate-Flex-Sky-Link-RS485.

What's inside

  • Installation
  • Wiring
  • Configuring
  • Mounting
  • Using with eGate
  • Configuration
  • eGate-Flex-T and eGate-Flex-T-RH modules
  • eGate-Flex-nSens module
  • Flex-Sky-Radio module
  • Sky configuration menu

Specifications

Measurement interval60–300 seconds recommended
Temperature unit°C or °F selectable
Maximum antenna gain2.5 dBi
Mounting screwsTwo screws 50 mm apart, max diameter 4.5 mm
nSens probe extension cableUp to 2 m
nSens probe firmware requirement2.00 or newer
Flex-Sky-Radio firmware requirement2.1 or newer
Recommended Sky transmission interval10 to 30 minutes

Frequently asked questions

How do I configure the eGate-Flex transmitter?

Connect a Nokeval DCS772 programming cable to the 3.5 mm jack in the measurement module and use the Nokeval Mekuwin software with Protocol=SCL, Baud=9600, Address=0, then click Save to EEPROM.

Which probes work with the eGate-Flex-nSens module?

The module accepts an eGate-nSens-HT-ENS or an eGate-nSens-HT-CSS humidity and temperature probe with firmware 2.00 or newer.

What radio technology do the Sky devices use?

The Sky devices use the Semtech LoRa modulation technique with the Nokeval NLORA1 protocol, so they are not compatible with LoRaWAN infrastructure.

How is the transmitter mounted?

Fasten the radio module to a surface with double-sided tape or with two screws 50 mm apart (maximum diameter 4.5 mm), avoiding metal surfaces near the radio module.

Download PDF (312 KB)