Eaton IZM20B3-V08F Air Circuit Breaker Datasheet

Datasheet for the Eaton IZM20B3-V08F 3-pole fixed air circuit breaker, 800 A, with IEC/EN 60947 ratings.


Eaton IZM20B3-V08F Air Circuit Breaker Datasheet - cover page
Brand
Eaton
Category
Other products
Document type
Datasheet
Language
English
Pages
3
File format
PDF
File size
221 KB
Published
23 November, 2026
Updated
23 November, 2026
MD5 checksum
039EAC9D15F9BA17B5CDBECDA4C36788

About this manual

This datasheet covers the Eaton IZM20B3-V08F circuit-breaker, a 3-pole, 800 A fixed air circuit-breaker/switch-disconnector in construction size IZM20 with selective protection and IEC approval.

It lists general, main conducting path, switching capacity, operating time, heat dissipation, weight, terminal capacity, and design verification data, plus links to tripping characteristics.

What's inside

  • Delivery program
  • Technical data
  • General
  • Main conducting paths
  • Switching capacity
  • Operating times
  • Heat dissipation at rated current I n
  • Weight
  • Terminal capacities
  • Design verification as per IEC/EN 61439

Specifications

Product rangeAir circuit-breakers/switch-disconnectors
Current range4000 to 6300 A
Protective functionSelective operation
Installation typeFixed
Construction sizeIZM20
Standard/ApprovalIEC
Number of poles3 pole
Degree of protectionIP20, IP55 with protective cover, IP41 with door sealing frame
Rated current (In = Iu)800 A
Rated uninterrupted current at 50 °C800 A
Rated uninterrupted current at 60 °C800 A
Rated uninterrupted current at 70 °C800 A
Rated ultimate short-circuit breaking capacity (Icu)50 kA
Rated service short-circuit breaking capacity (Ics)50 kA
Overload release, min. (Ir)320 A
Overload release, max. (Ir)800 A
Non-delayed short-circuit release (Ii)In x 2-10, OFF
Delayed short-circuit release (Isd)Ir x 2-10
StandardsIEC/EN 60947
Ambient temperature, storage-25 to +70 °C (-20 to +70 °C with LCD display)
Ambient temperature, operating (open)-25 to +70 °C (-20 to +70 °C with LCD display)
Mounting position / utilization categoryUtilization category B
Rated impulse withstand voltage (Uimp)8000 V AC
Rated operational voltage (Ue)690 V AC
Use in IT electrical power networks21 kA up to U = 440 V
Overvoltage category/pollution degreeIII/3
Rated insulation voltage (Ui)1000 V
Rated short-circuit making capacity (Icm) up to 440 V105 kA
Rated short-circuit making capacity (Icm) up to 690 V105 kA
Rated short-time withstand current (Icw), t = 1 s50 kA
Rated short-circuit breaking capacity (Icu)50 kA
Rated short-circuit breaking capacity (Ics)50 kA
Closing delay via spring release30 ms
Break time40 ms
Total opening delay via shunt release35 ms
Total opening delay via undervoltage release35/70 ms
Total opening delay on non-delayed short-circuit release35 ms
Maximum operating frequency60 operations/h
Heat dissipation, fixed mounting60 W
Heat dissipation, withdrawable units110 W
Weight, fixed mounting 3-pole43 kg
Weight, fixed mounting 4-pole54 kg
Weight, withdrawable 3-pole48 kg
Weight, withdrawable 4-pole62 kg
Weight, cassette 3-pole34 kg
Weight, cassette 4-pole38 kg
Terminal capacity, fixed mounting copper bar2 x 5 x 50 mm
Terminal capacity, withdrawable units copper bar2 x 5 x 50 mm
Design verification standardIEC/EN 61439

Frequently asked questions

What is the rated current of the IZM20B3-V08F?

The rated current (In = Iu) is 800 A.

What is the rated operational voltage?

The rated operational voltage (Ue) is 690 V AC.

Which standard does the breaker comply with?

It complies with IEC/EN 60947.

What is the degree of protection?

IP20, IP55 with protective cover, or IP41 with door sealing frame.

Download PDF (221 KB)