This Eaton technical data document covers the CX series conventional manual callpoints, including CXL and CXM variants, and declares conformity with EN54-11:2001+A1:2005 for fire alarm manual callpoints.
It lists operating voltage of 9 to 30VDC, switch characteristics of 470 ohms or 680 ohms with 3A SPCO, cable sizes from 0.28mm2 to 2.5mm2, ambient temperature ranges, ABS V0 material, and indoor IP24D or outdoor IP66 ratings. Callpoint accessories such as spacers, resettable plastic elements, clear hinged flaps, and bezels are also shown.
| Operating voltage | 9 to 30VDC |
|---|---|
| Switch characteristics | 470 ohms / 680 ohms, 3A SPCO |
| Cable size | FIRETUF, FP200 or MICC 0.28mm2 ~ 2.5mm2 |
| Ambient temperature | -10 °C to +55 °C (95%RH) or -25 °C to +70 °C (95%RH) |
| Material | ABS V0 |
| Environmental category indoor | IP24D |
| Environmental category outdoor | IP66 |
The operating voltage is 9 to 30VDC.
Indoor use is rated IP24D and outdoor use is rated IP66.
The range is -10 °C to +55 °C or -25 °C to +70 °C at 95%RH.
The callpoint material is ABS V0.