Operating manual for the Danfoss VLT HVAC Drive FC 100 High Power frequency converter, covering installation, programming, specifications, and alarms.
This operating manual covers the Danfoss VLT HVAC Drive FC 100 High Power frequency converter. It introduces the manual, safety instructions, mounting, electrical installation, programming via the local control panel, general specifications, and warnings and alarms.
The manual includes connection examples for start/stop, pulse start/stop, acceleration/deceleration, and potentiometer reference. It also provides parameter descriptions and states that the instructions apply to VLT HVAC frequency converters with software version 2.5x. This manual is written in Spanish.
| Software version | 2.5x |
|---|---|
| Ground leakage current | Greater than 3.5 mA |
| DC-link discharge wait time, 380–480 V, 110–200 kW | 20 minutes |
| DC-link discharge wait time, 380–480 V, 250–450 kW | 40 minutes |
| DC-link discharge wait time, 525–600 V, 110–250 kW | 20 minutes |
| DC-link discharge wait time, 525–600 V, 315–560 kW | 30 minutes |
The manual lists 20 or 40 minutes for 380–480 V units and 20 or 30 minutes for 525–600 V units, depending on power rating.
It can be seen in parameter 15-43.
It is greater than 3.5 mA.
It is not a safety switch and does not disconnect the frequency converter from the mains supply.