Danfoss VLT AQUA FC 200 Frequency Converter Programming Guide

Programming guide for Danfoss VLT AQUA FC 200 frequency converters, covering LCP operation, parameter setup, parameter lists, and troubleshooting.


Danfoss VLT AQUA FC 200 Frequency Converter Programming Guide - cover page
Brand
Danfoss
Category
inverter
Document type
Programming Manual
Language
Chinese
Pages
203
File format
PDF
File size
5.5 MB
Published
17 November, 2026
Updated
17 November, 2026
MD5 checksum
53ADFF7F9C11E064920B331ECAD483EF

About this manual

This programming guide applies to all FC 200 frequency converters with software version 1.9x. The software version can be checked in parameter 15-43 SWversion. It explains how to use the graphical and numerical local control panels and covers parameter descriptions, parameter lists, and troubleshooting.

The guide includes parameter groups from 0-** through 35-**, covering operation and display, motor, brake, reference/ramp, limits/warnings, digital and analog I/O, communication, smart logic control, application functions, multi-pump controller, and sensor input options. It also includes a parameter list and warning/alarm messages. This manual is written in Chinese.

What's inside

  • Introduction
  • How to Program
  • Graphical and Numerical Local Control Panel
  • Quick Menu
  • Main Menu Mode
  • Parameter Descriptions
  • Parameter List
  • Troubleshooting
  • Warning/Alarm Messages

Specifications

Software version1.9x
Applicable frequency convertersAll FC 200 frequency converters
Analog input current0-20 mA and 4-20 mA
Analog input voltage0-10 V DC
Analog output0-20 mA, 4-20 mA
Digital output signal24 V DC, max 40 mA

Frequently asked questions

What software version does this guide cover?

It covers all FC 200 frequency converters with software version 1.9x.

Where can I check the frequency converter software version?

The software version can be read in parameter 15-43 SWversion.

What does an asterisk mean in the parameter descriptions?

An asterisk marks a default setting.

How are factory default settings restored?

Run initialization through parameter 14-22 Operating Mode; the frequency converter then returns to default settings.