A quick guide for the installation and safety instructions of the Danfoss VLT 2800 frequency converter, covering high voltage warnings, electrical…
This document serves as a quick reference for installing and running the Danfoss VLT 2800 frequency converter. It emphasizes critical safety measures regarding high voltage and earth leakage currents before installation begins.
The guide provides specific instructions for mechanical installation, including dimensions for various unit types (VLT 2803-2882) and requirements for air passages. It also details electrical installation steps, such as connecting power mains to terminals L1, L2, L3, and earth to terminal 95, along with specific tightening torques.
You must wait at least 4 minutes before touching any potentially live parts.
A minimum 10mm² Cu or an additional PE wire with the same cable cross section as the Mains wiring must be used.
Only an RCD of Type B (time delayed) shall be used on the supply side of this product.