Danfoss VLT 2800 Series Frequency Converter HMI Connection Guide

Connection guide for linking Danfoss VLT 2800 frequency converters to DOP HMIs over RS-485, including communication settings and address definitions.


Danfoss VLT 2800 Series Frequency Converter HMI Connection Guide - cover page
Brand
Danfoss
Category
inverter
Document type
Installation Guide
Language
Chinese
Pages
4
File format
PDF
File size
143 KB
Published
10 November, 2026
Updated
10 November, 2026
MD5 checksum
17FAB49CD3BDCA55342B430B3849B5A3

About this manual

This guide explains how to connect Danfoss VLT 2800 series frequency converters to DOP human-machine interfaces. It lists the default communication settings as 9600, 8, Even, 1 (RS-485), with controller station number 1 and no control or status area.

The document gives RS-485 wiring for DOP-A/AE, DOP-AS57, DOP-AS35/AS38 and DOP-B series HMIs. It also defines read/write addresses for parameters, Control Word and Status Word registers, and bit contacts, with notes on Index handling and supported alarms. This manual is written in Chinese.

What's inside

  • Default HMI communication settings
  • Controller wiring
  • RS-485 wiring for DOP-A/AE series
  • RS-485 wiring for DOP-AS57 series
  • RS-485 wiring for DOP-AS35/AS38 series
  • RS-485 wiring for DOP-B series
  • Register and contact address definitions
  • Control Word and Status Word bits
  • Notes and restrictions

Specifications

Communication settings9600, 8, Even, 1 (RS-485)
Controller station number1
Control/status areaNone / None
Parameter read/write address rangeP0:0 – P3499:31; Double Word
Contact read/write address rangeP0:0.0 – P3499:31.31
Control Word addressCTRWD 0; Word
Status Word addressSTAWD 0; Word
Maximum alarm settings16

Frequently asked questions

What are the default communication settings for the Danfoss VLT 2800 connection?

The guide lists 9600, 8, Even, 1 over RS-485, with controller station number 1.

Which Danfoss VLT models does note 1 say the connection applies to?

Note 1 says it applies to VLT-2800, 5000, 6000 and 7000.

What happens if an Index No. is not entered for a parameter?

The default value 0 is used.

How many alarm settings are supported?

Alarm settings support up to 16 alarms, and more than 16 causes an error.