Connection guide for linking Danfoss VLT 2800 frequency converters to DOP HMIs over RS-485, including communication settings and address definitions.
This guide explains how to connect Danfoss VLT 2800 series frequency converters to DOP human-machine interfaces. It lists the default communication settings as 9600, 8, Even, 1 (RS-485), with controller station number 1 and no control or status area.
The document gives RS-485 wiring for DOP-A/AE, DOP-AS57, DOP-AS35/AS38 and DOP-B series HMIs. It also defines read/write addresses for parameters, Control Word and Status Word registers, and bit contacts, with notes on Index handling and supported alarms. This manual is written in Chinese.
| Communication settings | 9600, 8, Even, 1 (RS-485) |
|---|---|
| Controller station number | 1 |
| Control/status area | None / None |
| Parameter read/write address range | P0:0 – P3499:31; Double Word |
| Contact read/write address range | P0:0.0 – P3499:31.31 |
| Control Word address | CTRWD 0; Word |
| Status Word address | STAWD 0; Word |
| Maximum alarm settings | 16 |
The guide lists 9600, 8, Even, 1 over RS-485, with controller station number 1.
Note 1 says it applies to VLT-2800, 5000, 6000 and 7000.
The default value 0 is used.
Alarm settings support up to 16 alarms, and more than 16 causes an error.