Danfoss VLT MCD 500 Soft Starter Operating Manual

Operating manual for the Danfoss VLT MCD 500 soft starter, covering installation, wiring, programming, and troubleshooting for 7–800 kW motors.


Danfoss VLT MCD 500 Soft Starter Operating Manual - cover page
Brand
Danfoss
Category
motor starter
Document type
User Manual
Language
Chinese
Pages
85
File format
PDF
File size
2 MB
Published
11 November, 2026
Updated
11 November, 2026
MD5 checksum
1339598C70CC6BF79607873DA0DBA527

About this manual

This operating manual describes the Danfoss VLT MCD 500, an advanced digital soft starter for motors from 7 kW to 800 kW. The MCD 500 is offered in inline ratings from 21 A to 1600 A with inline or inside-delta connection, internal bypass up to 215 A, and mains voltages of 200–525 VAC or 380–690 VAC. It includes a full set of motor and system protection functions, and optional DeviceNet, Modbus, or Profibus communication modules are available.

The manual covers safety warnings, mechanical and electrical installation including fuse selection and wiring diagrams, application examples such as starting and stopping modes, braking, and jogging, the LCP display, parameter programming, tools such as the trip log and load/save settings, troubleshooting with trip messages, and specifications with accessories. The document number is MG.17.K1.41. This manual is written in Chinese.

What's inside

  • Safety
  • Introduction
  • Mechanical installation
  • Electrical installation
  • Application examples
  • Programming
  • Tools
  • Troubleshooting
  • Specifications
  • Accessories

Specifications

Motor power range7 kW to 800 kW
Current ratings (inline)21 A to 1600 A
Mains voltage200–525 VAC or 380–690 VAC
Control voltage24 VAC/VDC, 110–120 VAC, or 220–240 VAC
Internal bypassUp to 215 A
Relay outputs3 programmable relay outputs
Power output24 VDC, 200 mA
Event log99 entries with date and time stamp
Optional communication modulesDeviceNet, Modbus, or Profibus

Frequently asked questions

What motor sizes does the MCD 500 soft starter cover?

It is rated for motors from 7 kW to 800 kW.

Can power factor correction capacitors be connected to the MCD 500 output?

No. If static power factor correction is used, the equipment must be connected on the supply side of the soft starter.

How many entries can the event log store?

The event log stores 99 entries with date and time stamps.

Which communication modules can be fitted to the MCD 500?

Optional DeviceNet, Modbus, or Profibus communication modules are available.