Danfoss ETS 12.5 to ETS 400 electric expansion valve data sheet with technical data, capacities, wiring and accessories.
This data sheet describes the Danfoss ETS series of electric expansion valves for precise liquid injection in evaporators used in air conditioning and refrigeration applications. It covers features, technical data, valve construction, stepper motor switch sequence, wiring, and application with controllers and drivers.
The document lists rated capacities and code numbers for ETS 12.5, ETS 25, ETS 50, ETS 100, ETS 250 and ETS 400 valves, including R744 (CO2) versions, plus M12 connector cable accessories with jacket, insulation and length specifications.
| Compatible refrigerants | R410A, R407C, R404A, R507, R134a, R22, R1234ze; special valves for R744 (CO2) |
|---|---|
| Max. working pressure (PS/MWP) | ETS 12.5, ETS 25, ETS 50, ETS 100: 45.5 bar / 660 psig; ETS 250, ETS 400: 34 bar / 493 psig |
| Refrigerant temperature range | -40 °C to 65 °C (-40 °F to 149 °F) |
| Ambient temperature | -40 °C to 60 °C (-40 °F to 140 °F) |
| Motor enclosure | IP67 |
| Stepper motor type | Bi-polar - permanent magnet |
| Phase resistance | 52 Ω ±10% |
| Phase inductance | 85 mH |
| Step angle | 7.5° (motor), 0.9° (lead screw) |
| Nominal voltage | Constant voltage drive: 12 V dc -4% to 15%, 150 steps/sec |
| Phase current | Using chopper drive: 100 mA RMS -4% to 15% |
| Max. total power | Voltage / current drive: 5.5 / 1.3 W (UL: NEC class 2) |
| Step rate | Constant voltage drive: 150 steps/sec; chopper current drive: 0 - 300 steps/sec, 300 recommended |
| Total steps | ETS 12.5, ETS 25, ETS 50: 2625 steps; ETS 100: 3530 steps; ETS 250, ETS 400: 3810 steps |
| Full travel time | ETS 12.5, ETS 25, ETS 50: 17 / 8.5 sec.; ETS 100: 23 / 11.5 sec.; ETS 250, ETS 400: 25.4 / 12.7 sec. (voltage / current) |
| Lifting height | ETS 12.5, ETS 25, ETS 50: 13 mm; ETS 100: 16 mm; ETS 250, ETS 400: 17.2 mm |
| Electrical connection | M12 connector |
| Compatible Danfoss controllers | EKC 312, EKC 316A, EKD 316, EKD 316C and EXD 316 |
| Maximum cable length (Danfoss controllers) | 5 m / 15 feet for EKC 316A and EKC 312; 50 m / 150 feet for EKD 316 |
| Cable outer diameter | Special PVC cables: 5.0 mm (0.2 in.); CPE cables: 6.3 mm (0.25 in.) |
Compatible Danfoss controllers include EKC 312, EKC 316A, EKD 316, EKD 316C and EXD 316. The valve can also be driven by electronic control solutions from other manufacturers.
The ETS valve remains in the opening position it had at the moment of power failure unless a battery backup safety device is installed.
ETS 50 through ETS 400 are designed with a built-in sight glass with moisture indicator, while ETS 12.5 and ETS 25 do not feature a sight glass.
Operating the ETS series requires a controller with either 12 V DC voltage drive (5.5 W) or chopper current drive (100 mA RMS).