Danfoss Electric Expansion Valve ETS 12.5 - ETS 400 Data Sheet

Danfoss electric expansion valve data sheet for the ETS 12.5 - ETS 400 type, covering precise liquid injection, technical data, and compatible controllers.


Danfoss Electric Expansion Valve ETS 12.5 - ETS 400 Data Sheet - cover page
Brand
Danfoss
Category
Air conditioner
Document type
Datasheet
Language
English
Pages
18
File format
PDF
File size
2.7 MB
Published
25 November, 2026
Updated
25 November, 2026
MD5 checksum
FFDC364C83F1B8411F3DE6D5D9EDEFF3

About this manual

This Danfoss data sheet describes the electric expansion valve type ETS 12.5 - ETS 400. The ETS series is for precise liquid injection in evaporators for air conditioning and refrigeration applications. The valve uses a fully balanced piston and linear positioning design, with bi-flow capability and solenoid tight shut-off in both flow directions.

The data sheet lists features, technical data, approvals, design notes, motor switch sequences, electrical wiring, valve applications, and valve types. It notes compatibility with electronic control solutions from Danfoss and other manufacturers, and gives operating requirements, including controllers with 12 V DC voltage drive or chopper current drive.

What's inside

  • Features
  • Technical data
  • Approvals
  • Design Note
  • Electrical wiring
  • Valve application
  • Type
  • Rated capacity
  • Ordering

Specifications

Max. working pressure (PS/MWP)45.5 bar (660 psig) for ETS 12.5 to ETS 100; 34 bar (493 psig) for ETS 250 and ETS 400
Max. opening pressure differential (MOPD) normal flow33 bar (478.6 psi)
Inlet fluid temperature-40 °C – 65 °C (-40 °F – 149 °F)
Nominal voltage12 V dc -4% – 15%, 150 steps/sec.
Max. total power5.5 / 1.3 W (UL: NEC class 2)

Frequently asked questions

What refrigerants is the ETS series compatible with?

The ETS series has a wide range for all common refrigerants, and special valves for R744 (CO2) are available.

What is the max working pressure of the ETS valve?

ETS 12.5, ETS 25, ETS 50, and ETS 100 have a max working pressure of 45.5 bar / 660 psig, while ETS 250 and ETS 400 have 34 bar / 493 psig.

What happens during a power failure?

At power failure the ETS valve will remain in the opening position it has at the moment of power failure, unless a battery backup safety device is installed.

Download PDF (2.7 MB)