Danfoss ERC 211 Digital Controller Installation Guide

Installation guide for the Danfoss ERC 211 digital controller, covering technical features, quick-start configuration, wiring diagrams, and default settings…


Danfoss ERC 211 Digital Controller Installation Guide - cover page
Brand
Danfoss
Category
Other Electronics
Document type
Installation Guide
Language
Chinese
Pages
8
File format
PDF
File size
1.2 MB
Published
20 November, 2026
Updated
20 November, 2026
Model
ERC 211
MD5 checksum
0E274F963EDC0BADED0A45FD305547EC

About this manual

The Danfoss ERC 211 is a smart, multipurpose integrated refrigeration controller designed for operating temperature sensing control in commercial refrigeration and heating applications. It features a 16 A relay for direct connection of compressors up to 2 HP and supports various sensor types including NTC, PTC, and Pt1000. This manual is written in Chinese.

What's inside

  • Technical features
  • User interface
  • Quick-start configuration
  • Menu structure
  • Basic functions
  • Default application settings
  • Technical Data
  • Parameters

Specifications

Input voltage115 V AC or 230 V AC, 50/60 Hz
Rated powerLess than 0.7 W
Relay output16 A at 230 V
Measuring range-40 – 105 °C
Controller accuracy+/-0.5 K between -35 – 25 °C
Operating temperature-10 – 55 °C

Frequently asked questions

What are the available preinstalled applications?

The controller includes applications for cooling/heating without defrost, medium temperature with timed or air-temperature stop defrost, and heating thermostats.

Which sensor types are supported?

The controller supports NTC 5000 Ohms, NTC 10000 Ohms, PTC 990 Ohms, and Pt1000 sensors.

How do I initiate a manual defrost?

Press and hold the DEFROST button for 3 seconds to initiate a manual defrost.

What is the maximum compressor size supported?

The 16 A relay allows direct connection of compressors up to 2 HP based on motor power factor and efficiency.