ATC Diversified OVL-B bimetallic overload relays provide Trip Class 10 motor overload protection with IP20 terminals and CON Series contactor mounting.
ATC Diversified’s bimetallic overload relays provide thermal Trip Class 10 overload protection for single and three-phase motors, and phase loss protection for three-phase motors. The devices are UL Listed and CE marked, with visible trip indication, high-visibility labels, and IP20 guarded terminals.
The modular design permits direct mounting onto CON Series Contactors. Models OVL-B1 and OVL-B2 cover current ranges from 0.28 A to 50 A and include adjustable current settings, selectable manual or automatic reset, and a trip test function.
| Current Setting Range | 0.28 ~ 32 A (OVL-B1); 25 ~ 50 A (OVL-B2) |
|---|---|
| Trip Class | 10 |
| Rated Operating Voltage (UL/CSA) | 600 VAC |
| High Fault Short Circuit Current | 100 kA @ 480 V and 600 V |
| Number of Poles | 3 |
| Ambient Operating Temp. | -25 to +60 °C / -13 to +140 °F |
They use Trip Class 10 for reliable and accurate protection against overload conditions.
Yes, the modular design allows direct mounting onto CON Series Contactors.
Manual or automatic reset and test modes are available with a stop button.
It is 100 kA at 480 V and 600 V with Class J fuses.