ATC Diversified SLA Series phase voltage monitors protect 3-phase equipment against phase loss, under voltage, and phase reversal.
The ATC Diversified SLA Series is designed to protect 3-phase equipment against phase loss, under voltage, and phase reversal. With normal operating voltages applied in the proper ABC sequence, the internal relay energizes; incorrect phase sequence, phase loss, or voltages below drop-out levels de-energize it. Both Delta and Wye systems may be monitored, and neutral connections are not required in Wye systems.
The series includes multiple enclosure styles, adjustment types, operating voltages, and reset options, with ordering information listing drop-out voltages, output ratings, and agency approvals. On applicable models, an LED glows when all line conditions are normal, and the SLA Series is UL Listed under file number E55826.
| Drop-out voltage, 1-phase low | 83% of nominal |
|---|---|
| Drop-out voltage, 3-phase low | 90% of nominal |
| Response time, Style A and E up to 300 VAC | Operate 250 msec; release 0.5 sec |
| Response time, Style N | Operate 60 msec; release 0.5 sec |
| Power required, Style A | 3 VA (approximately) |
| Operating temperature | 32 to +131 F (0 to +55 C) |
| Storage temperature | -49 to 185 F (-45 to +85 C) |
| Output rating | SPDT (Style A and N); DPDT (Style E) |
| Phase sequence | ABC |
| Reset | Automatic (manual optional) |
| Indicator | LED glows when all conditions are normal |
| Agency approval | UL Listed under file number E55826 |
It protects 3-phase equipment against phase loss, under voltage, and phase reversal.
Yes, both Delta and Wye systems may be monitored.
No, connections to neutral are not required in Wye systems.
The required phase sequence is ABC.