A quick start guide for installing, starting up, and programming the Allen-Bradley PowerFlex 400 Adjustable Frequency AC Drive FRN 8.xx series.
This Quick Start guide provides a summary of the basic steps required to install, start-up, and program the PowerFlex 400 Adjustable Frequency AC Drive (FRN 8.xx). It is intended for qualified drive service personnel and does not replace the full User Manual. The document covers general precautions, mounting considerations, and wiring instructions.
| Maximum Surrounding Air Temperature (Open-Type) | -10° to 45°C (14° to 113°F) |
|---|---|
| Electrical Efficiency | 97.5% at rated amps, nominal line voltage |
| Control Output Frequency | 0-320 Hz (programmable) |
| Bus Overvoltage Trip (200-240V AC Input) | 405V DC bus voltage |
This guide is intended for qualified drive service personnel only.
No clearance is required between drives for Frame C.
The recommended fuse type is UL Class J, CC, T, or Type BS88.