Air Products and Controls MR-700 Series 12VDC/24VDC Relay Installation Guide

Installation guide for the Air Products and Controls MR-700 Series 12VDC/24VDC relay, with specifications, wiring, and approvals.


Air Products and Controls MR-700 Series 12VDC/24VDC Relay Installation Guide - cover page
Brand
Air Products and Controls
Category
RELAY
Document type
Installation Guide
Language
English
Pages
1
File format
PDF
File size
250 KB
Published
15 November, 2026
Updated
15 November, 2026
MD5 checksum
2DBB307C644D87E0EDC0D46F91CFD94F

About this manual

This document is an installation guide for the Air Products and Controls MR-700 Series 12VDC/24VDC relay. It lists product specifications, power requirements, ambient temperature limits, contact ratings, and construction details.

It also includes wiring information, an application example, caution and note statements, and approval information for the /S, /T, /C, and /C/R versions.

What's inside

  • Product Specifications
  • Power Requirements
  • Ambient Temperature
  • Contact Ratings
  • Contact Construction
  • Wiring
  • Application Example
  • Approvals

Specifications

Polarized coil input12VDC @ 17.5mA or 24VDC @ 21.2mA per module position
Ambient temperature32°F to 120°F (0°C to 49°C) at 93% RH, non-condensing/non-freezing
Contact ratingResistive load: 10 A @ 120V AC / 30VDC
Contact constructionDry form C SPDT per module position
Backbox18ga CRS, plated with 1/2 inch conduit knockouts top and bottom
MR-701 and MR-702 housingPlastic ABS 94V-0
MR-704 and MR-708 housingCRS 18ga
Energized indicatorOne red LED per module position
Approvals for /S and /T versionsUL Recognized Component (UL864, UOXX2), File #S3403
Approvals for /C and /C/R versionsUL Listed (UL864, UOXX), File #S3403; CSFM Listed, 7300-1004:1 10
Approvals for /C/R versionsMEA Accepted, 73-92-E Vol. 29

Frequently asked questions

What coil voltage and current does the MR-700 Series relay use?

It uses 12VDC at 17.5mA or 24VDC at 21.2mA per module position.

What is the contact rating?

The contacts are rated for a resistive load of 10 A at 120V AC or 30VDC.

What ambient conditions are supported?

The relay is rated for 32°F to 120°F (0°C to 49°C) at 93% RH, non-condensing and non-freezing.

Are the DC coil inputs polarized?

Yes, the DC coil inputs are polarized.

Download PDF (250 KB)